To run house circuits from a portable generator, three parts work together: a generator cord from the generator's twist-lock outlet, a power inlet box on the outside wall, and either a transfer switch or a panel interlock kit inside.

By Tom Calder · Updated November 8, 2026

Our picks

Best 30-amp generator cord 4.2
Generator to inlet box

Champion 100395 cord

Generator power cord, 25 ft, 30 A · 30 A · 7,500 W · L14-30P plug to L14-30R connector, generator to a manual transfer switch or inlet box

Generator to inlet box or switch, 25 ft

Researched
Best cord and inlet box set 4.2
Both parts in one box

CircleCord 10 ft cord and inlet box

Generator cord and inlet box set, 30 A · 30 A · 7,500 W · 10 ft L14-30P to L14-30R cord from the generator to the inlet box; the box is wired to a manual transfer switch or interlocked panel by a licensed electrician

Cord and inlet box in one set

Researched
Best power inlet box 4.3
The outside socket the cord plugs into

Connecticut Electric EGSPI30

Power inlet box, 30 A, NEMA 3R · 30 A · 7,500 W · NEMA L14-30 inlet; wired to a transfer switch or interlocked panel by a licensed electrician, with a generator cord from the generator

30A inlet for a manual transfer setup

Researched
Best interlock kit 3.9
Panel plate, fitted by an electrician

Natupal SD200A interlock

Generator interlock kit (panel mounted) · 200 A · Panel: Square D QO or Homeline, 150 or 200 amp · Mechanical plate on the panel so the main breaker and the generator breaker cannot both be on; a generator cord then runs from the generator to an inlet box wired to that breaker, installed by a licensed electrician

Fits only the listed panel

Researched

All 11 compared

Show
Power inlet box, 30 A, NEMA 3R · 30 A · 7,500 W · NEMA L14-30 inlet; wired to a transfer switch or interlocked panel by a licensed electrician, with a generator cord from the generator

30A inlet for a manual transfer setup

4.3
Our verdict
Our verdictResearched

A 30-amp NEMA 3R power inlet box with a hinged door, for generators up to 7,500 running watts. It is wired in by a licensed electrician and a generator cord runs from the generator to this inlet, never to a wall outlet. No cord is included.

Best for 30A inlet for a manual transfer setup

Good
  • NEMA 3R hinged door
  • ETL listed
  • Rated for generators up to 7,500 running watts
Worth knowing
  • No cord included
  • 30A only
  • Must be installed by a licensed electrician

Who shouldn't buy it: Don't buy it if you want to wire it yourself or have a 50A generator: installation is for a licensed electrician and this is a 30A inlet.

Generator power cord, 25 ft, 30 A · 30 A · 7,500 W · L14-30P plug to L14-30R connector, generator to a manual transfer switch or inlet box

Generator to inlet box or switch, 25 ft

4.2
Our verdict
Our verdictResearched

A 25 ft 30-amp generator cord from Champion for a manual transfer switch. The cord only ever runs from the generator to an inlet box or transfer switch, never to a wall outlet. The inlet box and switch are installed by a licensed electrician.

Best for Generator to inlet box or switch, 25 ft

Good
  • Champion-branded, 25 ft
  • 10 gauge, weather-resistant jacket
  • 1-year warranty
Worth knowing
  • Needs an inlet box or transfer switch already installed
  • 30A only
  • Listing's conductor count is inconsistent

Who shouldn't buy it: Don't buy it if your generator has no L14-30R outlet or your switch is 50A: this is a 30A L14-30 cord.

Generator cord and inlet box set, 30 A · 30 A · 7,500 W · 10 ft L14-30P to L14-30R cord from the generator to the inlet box; the box is wired to a manual transfer switch or interlocked panel by a licensed electrician

Cord and inlet box in one set

4.2
Our verdict
Our verdictResearched

A 10 ft 30-amp cord and a pre-drilled inlet box in one set. The box is wired in by a licensed electrician, and the cord only ever runs from the generator to the inlet box, never to a wall outlet. The short cord means the generator sits close to the box.

Best for Cord and inlet box in one set

Good
  • Cord and inlet box together
  • Rubber-plugged knockouts, no drilling
  • Storage bag and cord organizer
Worth knowing
  • 10 ft cord is short
  • 30A only
  • Must be installed by a licensed electrician

Who shouldn't buy it: Don't buy it if you need a longer cord or a 50A hookup: this is 10 ft and 30A.

Generator cord and inlet box set, 30 A · 30 A · 25 ft L14-30P to L14-30R cord from the generator to the inlet box; the box is wired to a transfer switch or interlocked panel by a licensed electrician

Cord and inlet box, 25 ft

4.1
Our verdict
Our verdictResearched

A 25 ft 30-amp cord and pre-drilled inlet box sold as a combo kit. The box is wired in by a licensed electrician, and the cord only ever runs from the generator to the inlet box, never to a wall outlet. The listing gives few specs.

Best for Cord and inlet box, 25 ft

Good
  • Cord and inlet box together
  • 25 ft cord
  • ETL listed
Worth knowing
  • Few specs in the listing
  • 30A only
  • Must be installed by a licensed electrician

Who shouldn't buy it: Don't buy it if you need wattage or model details first: the listing gives none.

Generator power cord, 50 ft, 30 A · 30 A · 7,500 W · L14-30P plug to L14-30R connector, generator to a manual transfer switch or inlet box

Long run from generator to inlet

4.0
Our verdict
Our verdictResearched

A 50 ft four-wire 30-amp generator cord with twist-lock ends and an ETL listing. The cord only ever runs from the generator to an inlet box or transfer switch, never to a wall outlet. The inlet box and switch are installed by a licensed electrician.

Best for Long run from generator to inlet

Good
  • 50 ft length
  • 4 conductors, 10 AWG
  • ETL listed
Worth knowing
  • Needs an inlet box or transfer switch already installed
  • 30A only
  • No warranty stated in the listing

Who shouldn't buy it: Don't buy it if you need the generator close to the house or a 50A connection: this is a 50 ft, 30A cord.

Generator power cord, 20 ft, 30 A · 30 A · 7,500 W · L14-30P plug to L14-30R connector, generator to a manual transfer switch or inlet box

Short 30A generator cord

4.0
Our verdict
Our verdictResearched

A 20 ft four-wire 30-amp twist-lock generator cord with a cord organizer. The cord only ever runs from the generator to an inlet box or transfer switch, never to a wall outlet. The inlet box and switch are installed by a licensed electrician.

Best for Short 30A generator cord

Good
  • 4 conductors, 10 gauge
  • ETL listed
  • Cord organizer included
Worth knowing
  • Needs an inlet box or transfer switch already installed
  • 30A only
  • No model number in the listing

Who shouldn't buy it: Don't buy it if you need more than 20 ft or a 50A cord: this is 20 ft and 30A.

Generator cord and inlet box set, 30 A · 30 A · 7,500 W · 15 ft L14-30P to L14-30R cord from the generator to the inlet box; the box is wired to a transfer switch or interlocked panel by a licensed electrician

Cord and inlet box, 15 ft

4.0
Our verdict
Our verdictResearched

A 15 ft 30-amp cord and a pre-drilled weatherproof inlet box. The box is wired in by a licensed electrician, and the cord only ever runs from the generator to the inlet box, never to a wall outlet.

Best for Cord and inlet box, 15 ft

Good
  • Cord and inlet box together
  • Pre-drilled holes
  • Rated -4 to 140 F
Worth knowing
  • 30A only
  • Listing's conductor count is inconsistent
  • Must be installed by a licensed electrician

Who shouldn't buy it: Don't buy it if you need a 50A hookup: this is a 30A L14-30 set.

Generator interlock kit (panel mounted) · 200 A · Panel: Square D QO or Homeline, 150 or 200 amp · Mechanical plate on the panel so the main breaker and the generator breaker cannot both be on; a generator cord then runs from the generator to an inlet box wired to that breaker, installed by a licensed electrician

Fits only the listed panel

3.9
Our verdict
Our verdictResearched

An interlock kit for Square D QO or Homeline, 150 or 200 amp. It is a plate that stops the main breaker and the generator breaker being on together. It fits only the panels listed, must be fitted by a licensed electrician, and the electrician should confirm the local inspector accepts a third-party kit for your panel.

Best for Fits only the listed panel

Good
  • Designed for the listed panel
  • Kit parts and labels included
  • 1 3/8 in spacing between main and generator breaker
Worth knowing
  • Fits only the panels listed
  • Must be fitted by a licensed electrician
  • Inspector approval of a third-party kit needs confirming

Who shouldn't buy it: Don't buy it if your panel is not exactly the one listed or your inspector does not accept third-party kits: it fits only Square D QO or Homeline, 150 or 200 amp.

Generator interlock kit (panel mounted) · 200 A · Panel: ITE, Gould, Murray, Siemens, Thomas and Betts, 150 or 200 amp · Mechanical plate on the panel so the main breaker and the generator breaker cannot both be on; a generator cord then runs from the generator to an inlet box wired to that breaker, installed by a licensed electrician

Fits only the listed panel

3.8
Our verdict
Our verdictResearched

An interlock kit for ITE, Gould, Murray, Siemens, Thomas and Betts, 150 or 200 amp. It is a plate that stops the main breaker and the generator breaker being on together. It fits only the panels listed, must be fitted by a licensed electrician, and the electrician should confirm the local inspector accepts a third-party kit for your panel.

Best for Fits only the listed panel

Good
  • Designed for the listed panel
  • Panel brands and breaker spacing stated in the listing
  • 1 1/4 in spacing between main and generator breaker
Worth knowing
  • Fits only the panels listed
  • Must be fitted by a licensed electrician
  • Inspector approval of a third-party kit needs confirming

Who shouldn't buy it: Don't buy it if your panel is not exactly the one listed or your inspector does not accept third-party kits: it fits only ITE, Gould, Murray, Siemens, Thomas and Betts, 150 or 200 amp.

Generator interlock kit (panel mounted) · 200 A · Panel: Eaton Cutler Hammer BR series, 150 and 200 amp · Mechanical plate on the panel so the main breaker and the generator breaker cannot both be on; a generator cord then runs from the generator to an inlet box wired to that breaker, installed by a licensed electrician

Fits only the listed panel

3.8
Our verdict
Our verdictResearched

An interlock kit for Eaton Cutler Hammer BR series, 150 and 200 amp. It is a plate that stops the main breaker and the generator breaker being on together. It fits only the panels listed, must be fitted by a licensed electrician, and the electrician should confirm the local inspector accepts a third-party kit for your panel.

Best for Fits only the listed panel

Good
  • Designed for the listed panel
  • Kit parts and labels included
  • 1 7/16 to 1 1/4 in spacing between main and generator breaker
Worth knowing
  • Fits only the panels listed
  • Must be fitted by a licensed electrician
  • Inspector approval of a third-party kit needs confirming

Who shouldn't buy it: Don't buy it if your panel is not exactly the one listed or your inspector does not accept third-party kits: it fits only Eaton Cutler Hammer BR series, 150 and 200 amp.

Generator interlock kit (panel mounted) · 100 A · Panel: Square D QO or Homeline, 100 or 125 amp · Mechanical plate on the panel so the main breaker and the generator breaker cannot both be on; a generator cord then runs from the generator to an inlet box wired to that breaker, installed by a licensed electrician

Fits only the listed panel

3.8
Our verdict
Our verdictResearched

An interlock kit for Square D QO or Homeline, 100 or 125 amp. It is a plate that stops the main breaker and the generator breaker being on together. It fits only the panels listed, must be fitted by a licensed electrician, and the electrician should confirm the local inspector accepts a third-party kit for your panel.

Best for Fits only the listed panel

Good
  • Designed for the listed panel
  • Kit parts and labels included
  • 3/4 to 7/8 in spacing between main and branch breakers
Worth knowing
  • Fits only the panels listed
  • Must be fitted by a licensed electrician
  • Inspector approval of a third-party kit needs confirming

Who shouldn't buy it: Don't buy it if your panel is not exactly the one listed or your inspector does not accept third-party kits: it fits only Square D QO or Homeline, 100 or 125 amp.

ⓘ As an Amazon Associate, PreparedStates earns from qualifying purchases. We may earn a commission when you buy through our links. When two products are close, commission can decide which one we pick. A clearly better product always wins. Amazon prices come from Amazon's own product data and can change at any time.

The rule that matters most
An inlet box, transfer switch or interlock kit is wiring work: OSHA says never to attach a generator to a building's electrical system unless a qualified electrician has properly installed it with a transfer switch, so have a licensed electrician fit it, with any permit your area needs. Never power house wiring by plugging a generator into a wall outlet, whatever cord is used: CPSC calls that backfeeding, says it is extremely dangerous, and warns it is an electrocution risk to utility workers and neighbors. If you only need a refrigerator and lamps, heavy-duty outdoor extension cords run straight from the generator, and you need none of this.

Before you buy

Match the plug to the outlet.

Many home backup generators have a 120/240V L14-30R (30-amp, four-prong twist-lock) outlet; the cords here have an L14-30P plug on the generator end and an L14-30R connector that plugs into the inlet box. A generator with only a 14-50R (50-amp) outlet needs a 50-amp cord and inlet box instead; we don't list one yet, though the Generac HomeLink 9854 kit on our transfer switch page includes a 50-amp inlet box.

Length: the generator has to stand outdoors, at least 20 feet from windows, doors and attached garages (Ready.gov).

CPSC says to use cords long enough to keep it far away from windows, doors and vents. Measure from where it will stand to the inlet box before you buy.

Check the cord's rating and gauge on its listing, and inspect it for cuts or damage before each use; OSHA says never to use frayed or damaged cords.

Inlet box: a weather-rated (NEMA 3R) box with a male L14-30 inlet, mounted outside and wired by a licensed electrician to a transfer switch or to the generator breaker of an interlocked panel.

Interlock kits are a metal plate on the breaker panel that stops the main breaker and the generator breaker being on together.

Each fits only certain panel brands and sizes: check yours, and have your electrician confirm your local inspector accepts a third-party kit for your panel.

Transfer switch or interlock?

A transfer switch kit powers a set number of chosen circuits; an interlock lets you pick any breakers in the panel, which makes it easier to overload the generator. Your electrician can advise on which suits your home.

Fit carbon monoxide alarms with battery backup on every level of your home before you run the generator.

How we choose

We verify every product's specifications against at least two independent sources, re-check its US price and stock on a schedule where we can track it automatically, and cross-check safety-relevant claims against official guidance. Every review is labeled Researched or Used and reviewed by us: where we've bought a product, or been sent it free, and used it ourselves, its review says which; where we haven't, our verdict is a considered spec-and-evidence comparison, not a hands-on test. When two products are close, commission can decide which one we pick. A clearly better product always wins. Read our full methodology →

Related gear comparisons

Guides that go with this

Common questions

What cord do I need to connect a generator to my house?

For a generator with an L14-30R outlet, a 30-amp cord with an L14-30P plug and an L14-30R connector, long enough for the generator to stand outdoors and well away from the house, plugged into a power inlet box a licensed electrician has wired to a transfer switch or interlocked panel.

Can I plug a generator into a dryer outlet or wall outlet?

No. CPSC says never to power house wiring by plugging a generator into a wall outlet, a practice known as backfeeding, which it calls extremely dangerous and an electrocution risk to utility workers and neighbors. It also bypasses some of the household circuit protection.

Is a generator interlock kit legal?

Rules are local. An interlock kit is wiring work on your panel: have a licensed electrician fit it, and ask them to confirm your local inspector accepts the kit for your panel. OSHA says never to attach a generator to a building's electrical system unless a qualified electrician has installed it with a transfer switch.

Do I need a 30-amp or 50-amp cord?

Match the generator's outlet and your inlet box. A 30-amp L14-30 setup covers generators with an L14-30R outlet; a generator whose 240V outlet is a 14-50R needs a 50-amp cord and inlet box.

How long should a generator cord be?

Long enough for the generator to stand outdoors and at least 20 feet from windows, doors and attached garages, as Ready.gov says. Measure the distance from that spot to your inlet box.